Level transmitters discrepancy
by
Published on 01-25-2011 08:09 PM

Originally Posted by
Sabeur
Dear All,
I'm C&I engineer working on Level transmitters Trouble shooting. The problem that:
I have level transmitters mounted on the same vessel at the same height but presenting some discrepancies.
I explain more the situation:
Each vessel has two DP level transmitters , same model ( Rosemount ): One for the safety and the other for control.
I will be very thankful if you give me your ideas and views concerning this.
Best Regards,

Originally Posted by
bitmap
Hi,
is the lower pressure port at the same pressure in both transmitters?
The span, LRV and URV of the transmitters is the same?
regards,

Originally Posted by
amshah
If everything is same then check, mounting zero.
your problem will be solved.

Originally Posted by
Sabeur
Thanks every body for your help,
@ bitmap:
not all of them having the same pressure tapping points.
But the problem consists that the given values are not adequate. I explain, when LT01 displays 50% the other must dispaly 30% (theoretically) but really it displays 15% for example.