It would be highly appreciated if some one could let me know these questions regarding the signals. Why we use 3-15 psi why not other limits i.e 0-15 psi? Why we use 4-20 mA why not other values i.e 0-20 mA?
the answer s simple in case we use 0-20 mA the zero stands for zero process variable, any damage happens to the connection also shows the zero even if there s some process variable presents, and the another reason is some current flow ll show by the system due to stray emf in the field. in second case we use 4-20mA, 4mA stands for 0% PV and the 0mA stands for broken lines or some dagage happened to lines or instrument... the reasons are same for pneumatic signals too......... hope u understand wat i explained dinil: dinilmurukesan@gmail.com
the 4- 20 scale s linear too.......