  2. amshah's Avatar
    : Make sure that u put your controller in manual and check, if your valve does not hunt then need to tune control loop.

    If u put your controller in manual mode and valve hunting remains then
    1) check air pressure setting through AFR. w.r.t to actuator requirement
    2) Check any leakage in air tubings /pipings or from actuators
    3) provide lubricating and greacing on stem
    make sure your gland packing is not providing friction to stem, loose gland follower nut (slightly).